Size: | Cable Entry: |
150, 200, 250, 300, 350, 400, 450 | Standard: M20 Option: 1/2"NPTF |
500, 600, 700..... 6000 mm | Grounding Resistance: |
Measuring Range: | Must be less than 10 |
Velocity 0-0.25 m/s Min. | Accuracy: |
0-12 m/s Max. | +/-2% of reading (Velocity>=0.5 m/s) |
Material: | +/-0.8% of Full Scale (F.S.>2 m/s) |
Protection Tube | +/-0.01 m/s (Velocity<0.5 m/s) |
Stainless Steel 316 | Repeatability: |
Screw | +/-0.4% of reading |
Stainless Steel 316 | Process Temperature: |
Electrode | -10~80 oC |
Stainless Steel 316L | Ambient Temperature: |
Cap | -25~70 oC |
PTFE | Max. Pressure: |
Ball Valve | 10 kgf/cm2 |
Stainless Steel 316 (Optional) | Conductivity: |
Hot-Tap Tool / Kit | More than 10 uS/cm |
Stainless Steel 304 (Optional) | Weight: |
Mounting: | 3-10 kg |
Compact or Remote | Coil Resistance: |
Process Connection: | 70-98 |
Threaded | Sensor Diameter: |
Threaded, 2" BSPP Female | 45 mm |
Flange | Sensor Length: |
Flange, JIS / ANSI / DIN | 310 mm (for 150-600 mm pipe ID) |
Installation: | 550 mm (for 600-2400 mm pipe ID) |
Direct insert to the pipe | 800 mm (for 2400-4200 mm pipe ID) |
Insert with Ball Valve | 1050 mm (for 4200-6000 mm pipe ID) |
Hot-Tap into pressurised pipe | |
Protection Class: | |
IP67 | |
IP68 (Submersible) | |
Explosion Proof: | |
Ex d (ib) ibq IIB T5 | |
(with AMC3200 only) |