Number of Inputs: | Display: |
3 Channels | 3.5" Mono-screen LCD with Backlit |
Flow Function: | Response Time: |
Input | 100 ms |
4-20 mA / Frequency (0-10 kHz) | Keypad: |
Display | 6 keys for programming and display |
5 Digits flowrate with decimal point | control |
13 Digits totalizer with decimal point | Engineer Unit: |
Accuracy | 21 different engineering units |
+/-0.1% of reading | Parameter Protection: |
Temperature Function: | 2 Password entries (6 Digits) for |
One or Two point (Energy calculator) | Supplier and User |
Input | Logging Rate: |
PT100 / 4-20 mA | 1-60 minutes Per Data |
Display | Recording Capability: |
4 digits temperature value with decimal point | 30 days (1 Data / minutes) |
Accuracy | 1800 days (1 Data / Hour) |
+/-0.1 oC | Storage Memory: |
Pressure Function: | 8 MB (on board) |
Input | Recycling Mode: |
4-20 mA | Newest data overwrites oldest data |
Display | Protection Class: |
5 Digits pressure value with decimal point | NEMA4 / IP65 (Fascia sealing) |
Accuracy | Weight: |
+/-0.1% of reading | 0.5 kg Maximum |
Calculation Function: | Dimensions: |
Ideal Gas, Temperature & Pressure Comp. | 96 mm (W) * 96 mm (H) *150 mm (D) |
General Gases, Temp & Pressure Comp. | Ambient Temperature: |
Natural Gas, NX-192 Formula | -10~60 oC |
Saturated Steam, Superheated Steam | Ambient Humidity: |
Liquid Mass, Density calculation | 10-85% RH (5-40 oC) |
Alarm Types: | Power Supply: |
High & Low alarm, Incr. & Decr. alarm | 85-260 VAC, 50/60 Hz |
Aux. Power Output: | Vibration Test: |
12 VDC / 24 VDC, 100 mA for Flow Transmitter | 10-60 Hz,10 m/s2 for 3 hours |
24 VDC, 100 mA for Temperature Transmitter | Power Consumption: |
24 VDC, 100 mA for Pressure Transmitter | <= 10 W |
Output: | Communication: |
4-20 mA, Load 750 W * 1 point | RS485 (MODBUS Protocol) |
Relay, 3 A / 250 V * 1 point | Parameter Storage: |
| Operation parameters are stored by |
| EEPROM for more than 10 years |