Process Fluid: | Display: |
Liquid, Gas, Vapor | 5 Digits programmable & 0-100% Bargraph |
Application: | Display Unit: |
Absolute Pressure, Gauge Pressure, | Standard 22 different engineering unit |
Vacuum | 5 Digits programmable for special unit |
Measuring Range: | Keypad: |
0-10 kPa~0-30 kPa (Minimum) | 3 Internal keys for Programming |
0-32 MPa~0-70 MPa (Maximum) | and output setting |
Turndown Ratio: | Current Output: |
100:1 | 4-20 mA 2 wires |
Accuracy: | with Hart Signal (Compatible) |
+/- 0.075% of span | Load |
Stability: | Rohm= (VDC-9) * 50 |
+/-0.15% of URL for 2 years | Power Supply: |
Working Temperature: | 9-36 VDC |
-25~95 oC | Digital Communication: |
Max. Pressure: | HART Protocol |
70 MPa | Damping: |
Material: | 0-32 Seconds |
Connection | Response Time: |
Stainless Steel 304 / Stainless Steel 316 | 100 ms |
Diaphragm | Mounting: |
Stainless Steel 316 / Tantalum | Direct installation or bracket on 2" Pipe |
Housing | Humidity Limit: |
Low copper cast aluminum alloy with | 0-100% Relative Humidity |
polyurethane, light blue paint | Turn on Time: |
Name / Tag Plate | 2 Seconds with minimum damping |
Stainless Steel 304 / Stainless Steel 316 | Zero Calibration: |
Cable Entry: | Automatic zero calibration by push-button |
M20 Conduit Threads / 1/2" NPT (Female) | Ambient Temperature: |
Process Connection: | -25~85 oC |
1/2" NPT, 1/2" BSP | Dimensions: |
Temperature Effect: | 102 mm (W) * 160 mm (H) * 130 mm (D) |
+/-0.18%~+/-0.5% of span per 20 oC | Weight: |
Over Pressure Limit: | 1.3 kg |
120% of Full Scale | Protection Class: |
Vibration Effect: | IP67 (Standard) |
+/-0.05% of URL per g to 200 Hz in any | Intrinsically Safe, Eex ia IIC T5 (Standard) |
axis | Explosion Proof, Ex d IIB T5 |
EMI / RFI Effect: | |
Follow SAMA PMC 33.1 from 20-1000 | |
MHz and for field strengths up to 30 V/m |