| Inputs: | Display: |
| Universal Input | Backlit LCD rotatable to any angle |
| Thermalcouple | Display Function: |
| T/C (K, S, B, E, J, T, R, N)...... | 5 Digits programmable & 0-100% Bargraph |
| RTD | Display Unit: |
| CU50 / PT100, 2 / 3 / 4 wire...... | oC / oF / oR / oK |
| mV | Setting Method: |
| -128~128 mV / -1000~1000 mV...... | B Type |
| Resistance | USB + PC software (windows system) |
0-600 / 0-5000 | C Type |
| Accuracy: | HART signal |
| +/-0.1% of span | D Type |
| Stability: | HART signal & keypad |
| +/-0.1% of span for 2 years | Current Output: |
| Temperature Effect: | 4-20 mA 2 wires with HART Signal |
| +/-0.1% of span per 10 oC | Load |
| CJC Compensation: | Rohm = (VDC-9) * 50 |
| +/-0.5 oC | Power Supply: |
| Simulation Output: | 9-36 VDC |
| 4-20 mA | Digital Communication: |
| Material: | HART Protocol |
| Wetted Parts | Cable Entry: |
| S.S. 304 / S.S. 316 / Has. C / Tantalum etc. | M20 Conduit Threads / 1/2" NPT (Female) |
| Housing | Damping: |
| Low copper aluminum alloy (Sprayed with | 0-32 Seconds |
| light blue polyurethane paint) | Response Time: |
| Module Housing | 100 ms |
| Flame-resistant PC | Turn on Time: |
| Name / Tag Plate | 2 Seconds with minimum damping |
| Stainless Steel 304 / Stainless Steel 316 | Zero Calibration: |
| Process Connection: | Automatic zero calibration by press-button |
| Threads / Flanges | Isolation: |
| Over Temp. Limit: | Input / Output / GND isolated to 480 VDC |
| 120% of Full Scale | Power Supply Effect: |
| Mounting: | +/-0.005 of Span per V |
| Direct mounting or bracket on 2" Pipe | Weight: |
| Humidity Limit: | 60 g (Converter only) with display |
| 0-100% Relative Humidity | 30 g (Converter only) without display |
| Ambient Temperature: | Protection Class: |
| -25~85 oC | IP67 (Standard) |
| Vibration Effect: | Intrinsically Safe, Eex ia IIC T5 (Standard) |
| +/-0.05% of URL per g to 200 Hz in any | Explosion proof, Ex d IIB T5 |
| axis | Sensor Connection: |
| EMI / RFI Effect: | M27 * 2 (Female) |
| Follow SAMA PMC 33.1 from 20-1000 | |
| MHz and for field strengths up to 30 V/m |